Error code
Classification
(hexadecimal)
812
Moderate error
H
813
Moderate error
H
814
Moderate error
H
Description and
Error name
cause
Either of the following
cases is the cause if the
value in CH Operation
mode setting (address:
0120
, 0140
) is 0, and
H
H
the value in CH Count
source selection (address:
0121
, 0141
) is 1 or 2.
H
H
• A value other than 0 and
4 is set in CH
Operation mode setting
(address: 0120
H
CH Count
0140
) of the other
H
source
channel.
coincidence
• A channel where CH
output setting
Count source selection
error
(address: 0121
H
0141
) is set is the
H
same as the channel
assigned to the
corresponding bit of
Coincidence output
channel assignment
setting (address:
0101
).
H
 indicates the channel
where settings are
incorrect.
A value other than 0 to 5 is
set in CH Pulse input
mode (address: 0122
CH Pulse
input mode
0142
).
H
setting error
 indicates the channel
where settings are
incorrect.
The setting in CH
Counting speed setting
(address: 0123
, 0143
H
is in one of the following
cases.
• If the value in CH
Pulse input mode
(address: 0122
H
0142
) is 0, 2, or 3, a
H
value other than 0 to 5 is
set.
CH Counting
• If the value in CH
speed setting
Pulse input mode
error
(address: 0122
H
0142
) is 1 or 4, a value
H
other than 0 to 6 is set.
• If the value in CH
Pulse input mode
(address: 0122
H
0142
) is 5, a value
H
other than 0 to 7 is set.
 indicates the channel
where settings are
incorrect.
Operation of when an error
occurs
The other
Error CH
CHs
,
*13
,
,
H
*13
)
H
,
*13
,
,
CHAPTER 11 TROUBLESHOOTING
Action
Take the following actions, and
turn off then on Initial data
setting request flag (RY9).
• Set CH Operation mode
setting (address: 0120
,
H
0140
) for the other channel
H
to 0 or 4.
• Set the corresponding bit of
Coincidence output channel
assignment setting (address:
0101
) to the channel where
H
CH Count source selection
(address: 0121
, 0141
) is
H
H
not set.
Set CH Pulse input mode
(address: 0122
, 0142
) to a
H
H
value between 0 and 5, and
turn off then on Initial data
setting request flag (RY9).
Take one of the following
actions on CH Counting
speed setting (address: 0123
0143
), and turn off then on
H
Initial data setting request flag
(RY9).
• If the value in CH Pulse
input mode (address: 0122
0142
) is 0, 2, or 3, set a
H
value between 0 and 5.
• If the value in CH Pulse
input mode (address: 0122
0142
) is 1 or 4, set a value
H
between 0 and 6.
• If the value in CH Pulse
input mode (address: 0122
0142
) is 5, set a value
H
between 0 and 7.
219