Counting speed setting can be done using the parameter setting. (
*2
Note that the count may be done incorrectly by inputting pulses whose phase difference is small between the phase A
pulse and phase B pulse. To check the input waveform of the phase A pulse and phase B pulse, or to check phase
difference between the phase A pulse and phase B pulse, refer to the following:
Page 30, Section 3.2.1
*3
The counting speed is affected by the pulse rise/fall time. The applicable counting speed is listed below.
Note that the count may be done incorrectly by counting pulses with long rise/fall time.
8Mpps
Counting speed
4Mpps
switch setting
2Mpps
Rise/fall time
t = 0.125µs
2Mpps
t = 0.25µs or less
1Mpps
t = 0.5µs or less
t = 1.25µs or less
t = 2.5µs or less
t = 25µs or less
t = 500µs
1Mpps
500kpps
200k
pps
Both 1- and 2-phase inputs
1Mpps
500kpps
200kpps
1Mpps
500kpps
200kpps
500kpps
500kpps
200kpps
200kpps
200kpps
100kpps
CHAPTER 3 SPECIFICATIONS
Page 80, Section 7.1)
100k
10k
*Counting speed = 1/T (pps)
pps
pps
100kpps
10kpps
100kpps
10kpps
100kpps
10kpps
100kpps
10kpps
100kpps
10kpps
10kpps
10kpps
500pps
T
t
t
29
3