Pulse Measurement Function

The pulse measurement function measures the ON width or OFF width of pulses that are input to the external input
terminals, CH Function input terminal (FUNC1, FUNC2) or CH Latch counter input terminal (LATCH1, LATCH2).
When the next pulse is measured, the measured value is written over the previous value.
Function input terminal
Latch counter input terminal
(1) Setting method of the pulse measurement function
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
2.
Set "CH Operation mode setting " to "3: Pulse Measurement Mode".
3.
Set the pulse width to be measured in "CH Pulse measurement setting (Function input
terminal)".
4.
Set the pulse width to be measured in "CH Pulse measurement setting (Latch counter input
terminal)".
156
(FUNC1/FUNC2)
Pulses
(LATCH1/LATCH2)
Pulses
[CC IE Field Configuration]
High-speed
counter module
Analysis
CH
(Function input terminal)
(RWr1C to RWr1D, RWr34 to RWr35)
Analysis
CH
(Latch counter input terminal)
(RWr1E to RWr1F, RWr36 to RWr37)
Select a high-speed counter module in "List of stations"
[Parameter Processing of Slave Station]
Remote register
Measured pulse value
Remote register