[Design Precautions]
● Do not install the communication cables together with the main circuit lines or power cables. Keep a
distance of 100mm or more between them. Failure to do so may result in malfunction due to noise.
● Do not install the control lines together with the main circuit lines or power cables. Keep a distance of
150mm or more between them. Failure to do so may result in malfunction due to noise.
[Installation Precautions]
● Shut off the external power supply (all phases) used in the system before mounting or removing a
module. Failure to do so may result in electric shock or cause the module to fail or malfunction.
[Installation Precautions]
● Use the module in an environment that meets the general specifications in the user's manual for the
module. Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of
the product.
● Do not directly touch any conductive parts and electronic components of the module. Doing so can
cause malfunction or failure of the module.
● Securely fix the module with a DIN rail.
● After the first use of the extension module, do not connect/disconnect the module more than 50 times
(in accordance with IEC 61131-2).
● To connect an extension module to a main module, engage the respective connectors and securely
lock the module joint levers. Incorrect connection may cause malfunction, failure, or drop of the
module.
● Securely connect the cable connectors. Poor contact may cause malfunction.
2
CAUTION
WARNING
CAUTION