Remote input
Signal name
(RX) No.
CH1
Update flag
(Latch count
value)
RX29
Update flag
(Sampling count
value)
RX41
CH2
Update flag
(Periodic pulse
count value)
244
• This signal turns on when CH Latch count value (RWr12 to RWr13, RWr2A to RWr2B) is
updated.
(
Page 133, Section 8.8,
CH Latch count value (RWr12 to RWr13, RWr2A to RWr2B) is updated without resetting
this flag.
• This signal turns off when CH Update flag reset command (Latch count value) (RY28,
RY40) is turned on.
*1
• Up to ΔT
delay occurs until this signal turns on after CH Latch count value (RWr12 to
1
RWr13, RWr2A to RWr2B) is updated.
(For the overview of the operation, refer to the description of CH Update flag reset
completed (Latch count value) (RX28, RX40).)
*1
For ΔT
, refer to Page 283, Appendix 4.
1
• This signal turns on when CH Sampling count value (RWr12 to RWr13, RWr2A to RWr2B)
is updated.
(
Page 136, Section 8.9)
• CH Sampling count value (RWr12 to RWr13, RWr2A to RWr2B) is updated without
resetting this flag.
• This signal turns off when CH Update flag reset command (Sampling count value) (RY28,
RY40) is turned on.
*1
• Up to ΔT
delay occurs until this signal turns on after CH Sampling count value (RWr12
1
to RWr13, RWr2A to RWr2B) is updated.
(For the overview of the operation, refer to the description of CH Update flag reset
completed (Sampling count value) (RX28, RX40).)
For ΔT
*1
, refer to Page 283, Appendix 4.
1
• This signal turns on when CH Periodic pulse count, difference value (RWr12 to RWr13,
RWr2A to RWr2B), CH Periodic pulse count, present value (RWr14 to RWr15, RWr2C to
RWr2D), and CH Periodic pulse count value update check (RWr16 to RWr17, RWr2E to
RWr2F) are updated.
(
Page 139, Section 8.10)
• CH Periodic pulse count, difference value (RWr12 to RWr13, RWr2A to RWr2B), CH
Periodic pulse count, present value (RWr14 to RWr15, RWr2C to RWr2D), and CH
Periodic pulse count value update check (RWr16 to RWr17, RWr2E to RWr2F) are updated
without resetting this flag.
• This signal turns off when CH Update flag reset command (Periodic pulse count value)
(RY28, RY40) is turned on.
*1
• Up to ΔT
delay occurs until this signal turns on after CH Periodic pulse count, difference
1
value (RWr12 to RWr13, RWr2A to RWr2B), CH Periodic pulse count, present value
(RWr14 to RWr15, RWr2C to RWr2D), and CH Periodic pulse count value update check
(RWr16 to RWr17, RWr2E to RWr2F) are updated.
(For the overview of the operation, refer to the description of CH Update flag reset
completed (Periodic pulse count value) (RX28, RX40).)
For ΔT
*1
, refer to Page 283, Appendix 4.
1
Description
Page 145, Section 8.12)

Advertisement