Mitsubishi NZ2GFCF-D62PD2 User Manual page 223

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

Error code
Classification
(hexadecimal)
826
Moderate error
H
D529
Major error
H
D52B
Major error
H
*1
Keeps its operation with the normal setting value just before the error.
*2
Stores -2147483648 or 2147483647 in CH Sampling count value (RWr12 to RWr13, RWr2A to RWr2B), CH Periodic
pulse count, difference value (RWr12 to RWr13, RWr2A to RWr2B), or CH Periodic pulse count value update check
(RWr16 to RWr17, RWr2E to RWr2F), and continues to count.
*3
Keeps its normal operation unless an error occurs.
*4
The ring counter function does not start counting.
*5
The linear counter function stops counting.
*6
Compares the count value with the normal setting value just before the error. The error does not affect Coincidence
output
assigned to the error CH and the other functions.
*7
Does not execute the cam switch function. The error does not affect the other functions.
*8
Executes the sampling counter function or periodic pulse counter function with the normal setting value just before the
error.
*9
Does not start to measure the frequency.
*10
Does not start to measure the rotation speed.
*11
Stops measuring pulses.
*12
Does not output the PWM waveform.
*13
Stops operations except the one on the error and updating EQU1 to EQU4 terminal status (RWr1), Cam switch output
signal (RWr2), Cam switch output terminal status (RWr3), CH Status (RWr20, RWr38), and CH External input status
(RWr21, RWr39).
*14
Continues its operation although the external output terminals of the extension output module are forced off. (Y0 LED to
YF LED on the extension output module turn on or off depending on the output status.)
*15
A minor error which can be reset by turning off then on CH Error reset command (RY36, RY4E)
*16
Stores 0 in all the monitor data and keeps 0 until the module operation information is initialized. The number of ON times
integration does not start.
Description and
Error name
cause
A value other than 00b to
10b is set in CH Latch
counter input response
CH Latch
time setting (address:
counter input
0129
.b4 to b5, 0149
H
response time
to b5).
setting error
 indicates the channel
where settings are
incorrect.
Communication
error 1
The communication LSI is
in failure.
Communication
error 2
Operation of when an error
occurs
The other
Error CH
CHs
.b4
*13
H
*13
*13
CHAPTER 11 TROUBLESHOOTING
Action
Set CH Latch counter input
response time setting (address:
0129
.b4 to b5, 0149
.b4 to
H
H
b5) to a value between 00b and
10b, and turn off then on Initial
data setting request flag (RY9).
• Malfunction due to noise may
be the cause. Check the
cable distance or grounding
condition of each device.
Then take measures against
noise.
• Conduct the unit test. If the
same error occurs again, a
hardware failure of the
module may be the cause.
Please consult your local
Mitsubishi representative.
221
11