Error code
Classification
(hexadecimal)
210
Moderate error
H
Moderate error
30
H
212
Description and
Error name
cause
The value in CH Ring
counter upper limit value
(RWw12 to RWw13,
RWw2A to RWw2B) is
CH Ring
smaller than the value in
counter
CH Ring counter lower
upper/lower
limit value (RWw10 to
limit value
RWw11, RWw28 to
setting error
RWw29) in the ring
counter function operation.
 indicates the channel
where settings are
incorrect.
A value other than 00b to
10b is set in Coincidence
output
of Coincidence
output comparison
Comparison
condition setting (address:
condition setting
0102
).
H
error
 indicates the channel
(Coincidence
where settings are
output
)
incorrect.
indicates the number of
Coincidence output on
which this error occurred.
Operation of when an error
occurs
The other
Error CH
CHs
If the
If the
parameters are
parameters are
written with the
written with the
parameter
parameter
processing of
processing of
the slave
the slave
station, or Initial
station, or Initial
data processing
data processing
completion flag
completion flag
(RY8) or Initial
(RY8) or Initial
data setting
data setting
request flag
request flag
(RY9) is turned
(RY9) is turned
*13
*13
off then on:
off then on:
If CH Count
If CH Count
enable
enable
command
command
(RY24, RY3C) is
(RY24, RY3C) is
turned off then
turned off then
*4
*3
on:
on:
*13
Action
Set the values that satisfy the
condition "CH Ring counter
lower limit value (RWw10 to
RWw11, RWw28 to RWw29) ≤
CH Ring counter upper limit
value (RWw12 to RWw13,
RWw2A to RWw2B)", and
perform one of the following
operations.
• If Initial data processing
request flag (RX8) is on, turn
off then on Initial data
processing completion flag
(RY8).
• If the parameters are written
with the parameter
processing of the slave
station, or Initial data setting
completion flag (RX9) is on,
turn off then on Initial data
setting request flag (RY9).
• If Initial data processing
request flag (RX8) and Initial
data setting completion flag
(RX9) are off, turn off then on
CH Count enable
command (RY24, RY3C).
Set coincidence output
of
Coincidence output comparison
condition setting (address:
0102
) to a value between 00b
H
and 10b, and turn off then on
Initial data setting request flag
(RY9).