(3) Comparison start timing of the coincidence output function
The coincidence output function starts comparison when "CH Operation mode setting" is set to "0: Normal
Mode", and when Initial data processing request flag (RX8) turns off then on.
The following table lists the timing of when the settings related to the coincidence output function are enabled.
Setting item
"Coincidence output 1 to 4 channel
assignment setting"
"Coincidence output 1 to 4 comparison
condition setting"
"Preset/replace setting at coincidence
output (Coincidence output 1 to 2)"
Point setting (Coincidence output 1 to 4)
(RWw0 to RWw1, RWw4 to RWw5,
RWw8 to RWw9, RWwC to RWwD)
Lower limit value setting (Coincidence
output 1 to 4)
(RWw0 to RWw1, RWw4 to RWw5,
RWw8 to RWw9, RWwC to RWwD)
Upper limit value setting (Coincidence
output 1 to 4)
(RWw2 to RWw3, RWw6 to RWw7,
RWwA to RWwB, RWwE to RWwF)
*1
When Initial data processing request flag (RX8) is on, the setting data is checked.
*2
When Initial data processing request flag (RX8) is on, the setting data is not checked.
*3
For details on the preset/replace (at coincidence output) function, refer to the following.
Page 114, Section 8.3.3
Timing of when settings are enabled
When Initial data
When Initial data
processing
setting request
completion flag
(RY8) is turned
turned off then
off then on
*3
*1
*1
*1
When Setting
change request
(Coincidence
flag (RY9) is
output 1 to 4)
(RY14 to RY17) is
on
turned off then on
*2
*2
*2
CHAPTER 8 FUNCTIONS
: Enable ⎯: Disable
Reference
Page 261, Appendix 2 (7),
Page 262, Appendix 2 (8)
Page 261, Appendix 2 (7),
Page 262, Appendix 2 (8)
Page 261, Appendix 2 (7),
Page 262, Appendix 2 (8)