Parameters And Function Diagrams For Faults And Alarms - Siemens sinamics dcp Operating Instructions Manual

Dc/dc power converter
Hide thumbs Also See for sinamics dcp:
Table of Contents

Advertisement

Triggering messages externally
If the appropriate binector input is interconnected with an input signal, fault 1, 2, or 3 or alarm
1, 2, or 3 can be triggered via an external input signal.
Once an external fault (1 to 3) has been triggered on the Control Unit drive object, this fault
is also present on all associated drive objects. If one of these external faults is triggered on a
different drive object, it is only present on that particular drive object.
BI: p2106
BI: p2107
BI: p2108
BI: p2112
BI: p2116
BI: p2117
Note
An external fault or alarm is triggered by a 1/0 signal.
An external fault and alarm do not usually mean that an internal message has been
generated. The cause of an external fault and alarm should therefore be corrected outside
the SINAMICS DCP.
8.14.3.4

Parameters and function diagrams for faults and alarms

Function diagrams (see SINAMICS DCP List Manual)
● 8060 Faults and alarms – fault buffer
● 8065 Faults and alarms – alarm buffer
● 8070 Faults and alarms – fault/alarm trigger word r2129
● 8075 Faults and alarms – fault/alarm configuration
Overview of important parameters (see SINAMICS DCP List Manual)
● r0944 Counter for fault buffer changes
...
● p0952 Fault incident counter
● p2100[0...19] Fault code for fault reaction selection
...
● r2139 Status word for faults
● r3120[0...63] Component number fault
● r3121[0...63] Component number alarm
SINAMICS DCP
Operating Instructions, 05/2016, A5E34382853K
→ External fault 1
→ External fault 2
→ External fault 3
→ External alarm 1
→ External alarm 2
→ External alarm 3
Operation
8.14 Diagnostics
→ F07860(A)
→ F07861(A)
→ F07862(A)
→ A07850(F)
→ A07851(F)
→ A07852(F)
257