Resonance Damping - Siemens SINAMICS G220 Operating Instructions Manual

Table of Contents

Advertisement

14.10.4.6

Resonance damping

Overview
Resonance damping reduces speed oscillations for a motor without load or for sudden load
changes.
Description of function
With p1349 > 0, resonance damping is active for the following output frequencies:
• Between 6% and 90% of the motor rated frequency f
• Maximum 45 Hz
With p1349 = 0, resonance damping is active for the following output frequencies:
• 95 % of the motor rated frequency f
• Maximum 45 Hz
Figure 14-114
Parameters
The following list contains the parameters of the "Resonance damping" function.
Number
r0066
r0078[0...1]
p0310[0...n]
p1338[0...n]
p1339[0...n]
p1349[0...n]
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
MotN
Resonance damping
Name
Output frequency
Current actual value torque-generating
Rated motor frequency
U/f mode resonance damping gain
U/f mode resonance damping filter time constant
U/f mode resonance damping maximum frequency
14.10 Closed-loop drive control
MotN
Unit
[Hz]
[Arms]
[Hz]
 
[ms]
[Hz]
Functions
505

Advertisement

Table of Contents
loading