Register No.
Control Selection Setting
bit 0
bit 1
bit 2
bit 3
000FH
bit 4 to B
bit C
bit D
bit E
bit F
0010H to 001AH
Reserved
001BH
Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)
001CH
Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)
001DH
Digital Output Option DO-A3 Output (Binary)
001EH to 001FH
Reserved
u

Monitor Data

Monitor data can be read only.
Register No.
Drive Status 1
bit 0
bit 1
bit 2
bit 3
bit 4
0020H
bit 5
bit 6
bit 7
bit 8 to bit D
bit E
bit F
Fault Contents 1
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
0021H
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Reserved
PID Setpoint Input
Torque reference / torque limit input (enables the setting from MEMOBUS/Modbus)
Torque compensation input (enables the setting from MEMOBUS/Modbus)
Reserved
Enable Terminal S5 Input for Broadcast Data
Enable Terminal S6 Input for Broadcast Data
Enable Terminal S7 Input for Broadcast Data
Enable Terminal S8 Input for Broadcast Data
During Run
During Reverse
Drive Ready
Fault
Data Setting Error
Multi-Function Contact Output (terminal M1-M2)
Multi-function Photocoupler output 1 Terminal P1 - PC
Multi-function Photocoupler output 2 Terminal P2 - PC
Reserved
ComRef status
ComCtrl status
Overcurrent (oC), Ground fault (GF)
Overvoltage (ov)
Drive Overload (oL2)
Overheat 1 (oH1), Drive Overheat Warning (oH2)
Dynamic Braking Transistor Fault (rr), Braking Resistor Overheat (rH)
Reserved
PID Feedback Loss (FbL / FbH)
EF to EF8: External Fault
CPFoo: Hardware Fault (includes oFx)
Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2 (UL3/
UL4)
PG Disconnected (PGo), PG Hardware Fault (PGoH), Overspeed (oS), Excessive Speed Deviation
(dEv)
Main Circuit Undervoltage (Uv)
Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault (Uv3)
Output Phase Loss (LF), Input Phase Loss (PF)
MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)
Operator Connection Fault (oPr)
B.9 MEMOBUS/Modbus Data Table