a. Slide the drive into the drive slot until it is fully seated.
b. Close the latch to lock the drive in place.
4. Return the drive to operation by doing one of the following:
If you cold-swapped the drive, restore power to the server. Complete the
procedure described in
If you hot-swapped the drive, configure it using the cfgadm -c configure
command. The following example shows the drive at c0::dsk/c1t1d0 being
configured.
# cfgadm -c configure c0::dsk/c1t1d0
Related Information
"Locate a Faulty Hard Disk Drive" on page 83
"Remove a Hard Disk Drive" on page 86
"Remove a Hard Disk Drive Filler Panel" on page 84
"Install a Hard Disk Drive Filler Panel" on page 90
"Verify Hard Disk Drive Functionality" on page 91