Data Type
Select the data type to be handled by the operation selected for Action Mode.
For details, refer to Chapter 2 "1.1 Available Data" on page 2-1.
UBIN16(W) and UBIN32(D) can only be set if Action Mode is set to OR, AND, or XOR.
UBIN16(W) and UBIN32(D) can only be set if Action Mode is set to Move. Because the number of
device addresses to transfer is specified in Advanced mode, you do not need to set Data Type.
If BCD4(B), BCD8(EB), or Float32(F) is selected and the arithmetic data contains a value inexpressible
in BCD, a 1 is written to the System Area 2 Processing error bit (address number+2, bit 5) and an error
message is displayed. For details, refer to Chapter 4 "Processing error" on page 4-32 and Chapter 36
"Processing error" on page 36-3.
Source 1
Specify the source word device.
Click
to display the Tag Editor. For the device address configuration procedure, refer to Chapter 2 "5.1 Device
Address Settings" on page 2-70.
This setting is enabled only if Action Mode is set to Add, Sub, Multi, Div, Mod, OR, AND, or XOR.
Source Data
Select the data to be handled by the operation selected for Action Mode.
Value:
Use a constant value.
Only a Value can be handled if Action Mode is set to Set, Momentary, or Alternate.
If Action Mode is set to Momentary or Alternate, the value in the ON Data is written when the
button is ON, and the value in the OFF Data is written when the button is OFF.
Hexadecimal:
Device Address: Use a value of device address.
Specify the device address.
Click
2 "5.1 Device Address Settings" on page 2-70.
Use Reference Device Address
Transfer
*1 Advanced mode only
Select this check box to enter the ON Data and OFF Data values in
hexadecimal.
to display the Tag Editor. For the device address configuration procedure, refer to Chapter
*1
:Select this check box and specify a device address to change the
source word device according to the value of the specified device
address.
This setting is enabled only if Action Mode is set to Move.
For details, refer to Chapter 2 "Indirect Read and Indirect Write
Settings" on page 2-5.
*1
:
Specify the number of word devices (1 to 64) to transfer.
This setting is enabled only if Action Mode is set to Move.
Example: If Transfer is set to 2 and Write is set to 3, the same data in
Device Address: LDR0
Transfer: 2
Destination Device: D100
Write: 3
WindO/I-NV4 User's Manual
2 continuous word device addresses will be written to the
destination device address 3 times.
LDR0
LDR1
2 Word Button
999
D100
999
1000
D101
1000
D102
999
D103
1000
D104
999
D105
1000
8-25
8