3 Project Settings Dialog Box
Time Zone
Select the time zone to set. (Default: (UTC) Coordinated Universal Time)
Enable Daylight Saving Time:
When the Enable Daylight Saving Time check box is selected, the following date and time in the Alarm Log,
Data Log, and Operation Log functions may appear to log data at the same time twice, or to have
advanced in time and no data has been logged. This is due to the daylight saving time correction.
• Date and time when output as a CSV file
• Output date and time added to the CSV file name
• Date and time displayed on the part
• The daylight saving time system is subject to change, therefore check the dates and times displayed in
Start and End.
• IANA Time Zone Database version number 2019a is adopted.
Checking the communication contents with the SNTP server
You can check the communication contents with the SNTP server through the values of the HMI Special Internal
Relays and the HMI Special Data Registers.
LSM57
When the value of this bit changes from 0 to 1, get the current time from the SNTP server. The acquired current time
is written to the MICRO/I internal clock and stored in the MICRO/I internal current time data (LSD13 to 19).
LSD29
The execution result of communication with the SNTP server is stored.
Status
0: Successfully Completed
2: Timeout error
4: Other error
LSD30
The elapsed time (0 to 65535 minutes) from the time last obtained from the SNTP server to the current time is stored.
If the current time is successfully obtained, the value will be reset and the elapsed time will start counting. Even if it
fails to get the current time, the elapsed time counting continues without interruption until it succeeds.
4-82
Select this check box to correct the time to daylight saving time when it exists in the
selected time zone.
Start: Displays the start date and time of daylight saving time.
End:
Displays the end date and time of daylight saving time.
The SNTP server does not return a response after the timeout period (30 seconds) has
elapsed due to the following reasons.
• An Ethernet cable is disconnected.
• Host Name of the SNTP server is incorrect.
• IP address of the SNTP server is incorrect.
• A connection cannot be made to the preferred DNS server and alternate DNS server.
MICRO/I cannot perform communication with SNTP server