IDEC WindO/I-NV4 User Manual page 153

Automation organizer
Table of Contents

Advertisement

Example: When Trigger Type in Trigger Condition is While ON, Device Address is LM100, Status Device
Address is LDR110, Completed Device Address is LM101 and the Not Clear Completed Device
Address automatically check box is not selected
When Status Device Address is LDR110, error information and time out information is stored in each
bit of LDR110.
When receiving of 1 frame of data is completed before the Receiving Time Out duration has elapsed
from when the trigger condition is satisfied, the value of the Receiving Time Out of the Status Device
Address LDR110 (address number+0, bit 14) remains 0.
Value of Device Address LM100 when
Trigger Condition is While ON
Value of Receiving Time Out
(address number+0, bit 14)
of Status Device Address LDR110
Value of Completed Device Address LM101
When receiving of 1 frame of data could not be completed by the time the Receiving Time Out duration
elapses from when the trigger condition is satisfied, the value of the Receiving Time Out of the Status
Device Address LDR110 (address number+0, bit 14) changes to 1.
Value of Device Address LM100 when
Trigger Condition is While ON
Value of Receiving Time Out
(address number+0, bit 14)
of Status Device Address LDR110
Value of Completed Device Address LM101
Value of Device Address LM100 when
Trigger Condition is While ON
Value of Receiving Time Out
(address number+0, bit 14)
of Status Device Address LDR110
Value of Completed Device Address LM101
Enter a comment for a command. The maximum number is 40 characters.
Comment:
Receive data 1 frame
Receive command
1
0
1
0
1
0
Receive command
1
0
1
0
1
0
Receive command
1
0
1
0
1
0
WindO/I-NV4 User's Manual
Receiving Time Out duration
Receive data 1 frame
Receiving Time Out duration
Receive data 1 frame
Receiving Time Out duration
Receive data 1 frame
5 User Communication
3
3-45