Allocate device addresses to Present_Value
Select Enable in the Device Control of Present_Value, and then click a button displayed in Device to display the
Present_Value Settings dialog box. Configure the parameters in the Present_Value Settings dialog box.
Device for Present_Value
Configures the device address to store Present_Value.
According to Conversion type, 1 or 2 continuous words of address number are used starting from the specified
address number of Device Address.
Device for Present_Value
Present_Value for writing
Specify the Top Device Address so that the address number of device address is not exceeded.
Conversion type
Configures the data type of the device address to which Present_Value (float) is allocated. For details, refer to
Present_Value in "Analog Input Object" on page 3-136.
Coefficient
Configures Present_Value as the product of the value stored in the device address multiplied by the coefficient.
Present_Value = Value stored in the device address × Coefficient
Example:
Device Address
#D0000
UBIN16(W)
#D0000, #D0001
Float32(F)
The coefficient is multiplied as a Float32(F) value. The conversion order is as follows.
Device Addresses → Present_Value
(1) The value of the device addresses is converted to a
(2) The coefficient is multiplied by the conversion result in (1).
Conversion type
UBIN16(W), BIN16(I)
UBIN32(D), BIN32(L), Float32(F)
Data Type
Value
1000
2.5
Float32(F)
WindO/I-NV4 User's Manual
7 BACnet Communication
Storage Destination
The address number of Top Device Address+0
The address number of Top Device Address+0,
The address number of Top Device Address+1
Coefficient
0.01
0.5
value.
3
Present_Value
10.0
1.25