Allocate device addresses to Present_Value
Select Enable in the Device Control of Present_Value, and then click a button displayed in Device to display the
Present_Value Settings dialog box. Configure the parameters in the Present_Value Settings dialog box.
■
Device for Present_Value
Configures the device address to store Present_Value.
According to Conversion type, 1 or 2 continuous words of address number are used starting from the specified
address number of Device Address.
Device for Present_Value
Present_Value for writing
Specify the Top Device Address so that the address number of device address is not exceeded.
■
Conversion type
Configures the data type of the device address to which Present_Value (float) is allocated. For details, refer to
Present_Value in "Analog Input Object" on page 3-136.
■
Coefficient
Configures Present_Value as the product of the value stored in the device address multiplied by the coefficient.
Present_Value = Value stored in the device address × Coefficient
Example:
Device Address
#D0000
UBIN16(W)
#D0000, #D0001
Float32(F)
The coefficient is multiplied as a Float32(F) value. The conversion order is as follows.
Device Addresses → Present_Value
(1) The value of the device addresses is converted to a
(2) The coefficient is multiplied by the conversion result in (1).
Conversion type
UBIN16(W), BIN16(I)
UBIN32(D), BIN32(L), Float32(F)
Data Type
Value
1000
2.5
Float32(F)
WindO/I-NV4 User's Manual
7 BACnet Communication
Storage Destination
The address number of Top Device Address+0
The address number of Top Device Address+0,
The address number of Top Device Address+1
Coefficient
0.01
0.5
value.
3
Present_Value
10.0
1.25
3-113