3 Project Settings Dialog Box
• When using the MICRO/I as UDP, the MICRO/I cannot automatically identify and reply to the IP address
and port number of the external device. UDP broadcasting is also not supported.
• For TCP client and TCP server, make a 1:1 connection between the MICRO/I and the external device for
one user communication setting.
• When the Change IP Address and Port Number by Device Address check box is selected, the
changed IP address and port number are reflected when data is next sent.
• Regarding TCP port number of MICRO/I, note the following points.
The numbers that cannot be used: - 2539: Maintenance communication (Data Transfer)
Duplicate numbers cannot be configured in the following functions:
• Duplicate UDP port numbers of MICRO/I cannot be configured in the following functions.
- UDP is selected for the User Communication ( refer to "Port No." on page 4-43)
- IDEC System as Manufacture and DM LINK Ethernet(UDP) as Communication Driver are
selected on the Communication Driver tab
( refer to the WindO/I-NV4 External Device Setup Manual)
- OMRON as Manufacture and SYSMAC CS1/CJ series(Ethernet) as Communication Driver are
selected on the Communication Driver tab
( refer to the WindO/I-NV4 External Device Setup Manual)
• The connection status for TCP clients and the TCP server can be checked with the value of the HMI
Special Data Registers (LSD). The connection is disconnected when 0. The connection is connected when
1.
LSD67-0: Connection status for User Communication 1 set to Ethernet interface
LSD67-1: Connection status for User Communication 2 set to Ethernet interface
LSD67-2: Connection status for User Communication 3 set to Ethernet interface
• To forcibly disconnect the connection with TCP clients and the TCP server, set the value of the HMI Special
Data Registers (LSD) from 0 to 1.
LSD68-0: User Communication 1 set to Ethernet interface
LSD68-1: User Communication 2 set to Ethernet interface
LSD68-2: User Communication 3 set to Ethernet interface
4-44
- 2538: For pass-through
- 2101: For FC4A Series MicroSmart direct connection pass-through
- Maintenance communication
( refer to "Port Number" on page 4-41)
- Web server function ( refer to "Port Number" on page 4-67)
- FTP server function ( refer to "Port Number" on page 4-68)
- TCP Server is selected for the User Communication
( refer to "Port No." on page 4-43)
- Modbus as Manufacture and Modbus TCP Server as
Communication Driver are selected on the Communication
Driver tab
( refer to the WindO/I-NV4 External Device Setup Manual)
- YASKAWA Electric as Manufacture and MP2000(Ethernet)
as Communication Driver are selected on the Communication
Driver tab
( refer to the WindO/I-NV4 External Device Setup Manual)