IDEC WindO/I-NV4 User Manual page 287

Automation organizer
Table of Contents

Advertisement

Address
Bit
number
Flash display
2
(0.5 sec. cycle)
3 to 4
Reserved
5
Backlight auto off
+1
6
Beep
7
Screen display
8
Reserved
9
Clear error
Numerical input setting
10
clear
Character input setting
11
clear
12 to 15
Reserved
Function
This bit stores the screen flash state (0.5 sec. cycle). Write a value to this
bit to change the state. This bit is 0 immediately after the power is turned
on.
0:
Do not flash
Stop flashing the screen and turn it on.
1:
Flash
Flashes the screen in 0.5 second intervals.
When the Flash display (1 sec. cycle) (address number+1, bit 1) and
the Flash display (0.5 sec. cycle) (address number+1, bit 2) are both
1, the screen flashes at one second intervals.
This bit stores whether or not the function to automatically turn off the
backlight is enabled when the Auto OFF check box is selected under
Backlight in the Project Settings dialog box. Write a value to this bit
to change the state. This bit is 0 immediately after the power is turned
on.
0:
Enabled
Automatically turns off the backlight when the MICRO/I is unused
for an extended period of time.
1:
Disabled
Does not automatically turn off the backlight when the
MICRO/I is unused for an extended period of time. The backlight
turns on if the value changes to 1 when the backlight is off.
This bit stores the beep state. Write a value to this bit to change the
state. This bit is 0 immediately after the power is turned on.
0:
Stop
Stops continuous beeping.
1:
Beep
Starts continuous beeping.
This bit stores the screen display state. Write a value to this bit to change
the state.
0:
Hide
Hides the screen when the backlight is on.
1:
Show
Displays the screen.
Write 1 to this bit to clear the error information bit (System Area 2,
address number+2). This bit automatically changes to 0 when processing
is finished.
Write 1 to this bit to clear the Numerical input setting complete bit
(System Area 2 address number+3, bit 0) and the Numerical input setting
cancel bit (System Area 2 address number+3, bit 1). This bit
automatically changes to 0 when processing is finished.
Write 1 to this bit to clear the Character input setting complete bit
(System Area 2 address number+3, bit 5) and the Character input setting
cancel bit (System Area 2 address number+3, bit 6). This bit
automatically changes to 0 when processing is finished.
WindO/I-NV4 User's Manual
3 Project Settings Dialog Box
Description
4
4-31

Advertisement

Table of Contents
loading

Table of Contents