Allocate device addresses to Present_Value
Configure the parameters in the Present_Value Settings dialog box.
■
Device for Present_Value
Configures the device address to store Present_Value.
According to Conversion type, 1 or 2 continuous words of address number are used starting from the specified
address number of Device Address.
Device for Present_Value
Present_Value for reading
Specify the Top Device Address so that the address number of device address is not exceeded.
■
Conversion type
Configures the data type of the device addresses to which Present_Value (float) is allocated. For details, refer to
Present_Value in "Analog Output Object" on page 3-137.
■
Coefficient
The product of Present_Value multiplied by 1/coefficient multiplied is stored in the device addresses.
Value of device addresses = Present_Value × (1/coefficient)
Example:
Present_Value
10.0
0.01
1.25
0.5
The coefficient is multiplied as a Float32(F) value. The conversion order is as follows.
Present_Value → Device Addresses
(1) Present_Value is multiplied by (1/coefficient).
(2) The data type of the result of (1) (Float32(F)) is converted.
Conversion type
UBIN16(W), BIN16(I)
UBIN32(D), BIN32(L), Float32(F)
Coefficient
Device Addresses
#D0000
#D0000, #D0001
WindO/I-NV4 User's Manual
7 BACnet Communication
Storage Destination
The address number of Top Device Address+0
The address number of Top Device Address+0,
The address number of Top Device Address+1
Data Type
UBIN16(W)
1000
Float32(F)
2.5
3
Value
3-115