1 Numerical Input
Focus is moved by ENT button
When multiple Numerical Inputs are configured on the screen, select this check box to continue entering values on
each of the Numerical Inputs.
Each time ENT is pressed, the focus moves between the Numerical Inputs according to Focus Order. On the View
tab, in the Screens group, click Focus Order, and then click the Numerical Inputs in the order to move the focus.
Example: When Numerical Input A and B are configured and the Focus is moved by ENT button check box for
Numerical Input A is selected and the Focus is moved by ENT button check box for Numerical Input B is
cleared
A
B
Operations
and display
Display value of
Numerical Input A
device address
action
(Display mode)
Display value of
Numerical Input B
device address
action
(Display mode)
Numerical Input A
Value of
1234
Destination Device Address
Numerical Input B
567
Value of
Destination Device Address
Update the display by ENT button
Select this check box to display the current value unchanged and update the display when a value is entered and ENT
is pressed.
When this check box is cleared, the display updates with each press of a number button to display the number being
entered.
Numerical Input
Keypad display
Operations and display
Action
Value of
Destination Device Address
Numerical Input display
Keypad display
When a value outside the input range is entered and ENT is pressed, the symbol selected under Symbol to
show when out of range or Error occurs is displayed. The value is not written to the device address.
*1 Advanced mode only
10-8
*1
Press Numerical Input A
Enter a value
1234
1234
1234
567
567
567
1234
Display value of
Display focus
device address
(Entry mode)
(Entry mode)
1234
1234
567
567
*1
Press Numerical Input
1234
1234
1234
Display value of
Display focus
device address
(Entry mode)
(Display mode)
1234
1234
1234
1234
-
1234
WindO/I-NV4 User's Manual
Press ENT
999
999
567
567
999
999
567
Move focus from
Numerical Input A to B
Write value to
Display value of
device address
device address
(Entry mode)
(Display mode)
Display focus
(Entry mode)
999
999
567
567
Enter a value
Press ENT
1234
999
Display value of
Write value to
device address
device address
(Entry mode)
(Entry mode)
1234
999
1234
999
999
999
Enter a value
Press ENT
999
999
567
333
333
333
Display value of
Write value to
device address
device address
(Entry mode)
(Entry mode)
999
999
567
333
999
999
999
Display value of
device address
(Display mode)
999
999
-
Press CAN
999
333
333
Close Standard
Keypad
Display value of
device address
(Display mode)
999
333