Download Print this page

Power Controller - Siemens SIRIUS 3RF29 0-0KA Series Operating Instructions Manual

Power controller

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 2
SIRIUS

Power controller

Operating Instructions
Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Disconnect power before working on equipment.
CAUTION
Reliable functioning of the equipment is only ensured with
certified components.
Assembly / disassembly
Carry out assembly / disassembly in the order shown in Fig. I. Observe
the position of the electrical contacts (assembly step 1)
Circuit diagram
Fig. IIa (solid shaft operation), Fig. IIb (phase angle)
Dimension drawings
Fig. V: Dimensions in mm, (in)
Conductor cross-sections and tightening torques
Fig. VI
Commissioning
1. Connect the conductors as shown in the examples in Fig. IIa and
Fig. IIb.
2. The following setpoint options (setpoint value in % of the stored refe-
rence power rating of the loads) are available for the power control:
• If the setting switch "P" is in the 0 % position (left stop), enter the
setpoint value of 0 to 10 V (0 to 100 %) via an external analog
signal (terminal "10 V +" and "IN / 0 –"), refer to Fig. IIb.
• If the setting switch "P" is in the > 0 % position, enter the setpoint
value via the setting switch "P". It is switched on via the "IN / 0 –"
input. The analog input "10 V +" is not switched.
3. The following operating mode options are available:
• Fig. IIa: solid shaft operation
with setting switch position "t
(Ramp time = 0 s).
• Fig. IIb: phase angle
with setting switch position "t
max. 10 s for the inrush current limitation. The ramp time is only
active during switch-on and refers to 100 % of the setpoint value.
NOTICE
Modified settings will not take effect until the next switch-on. In
phase angle control operating mode, a reactor is required to
comply with limit values of the wire-bound interference voltage
(refer to Fig. IIb).
4. After applying voltage to A1 / A2 (24 V AC / DC or 110 V AC), and
before the first teaching procedure, the thyristor fault (THYRISTOR)
and supply fault (SUPPLY) LEDs will flash alternatingly every 0.5 s,
since no reference power rating (100 %) has yet been stored
(taught) in the device, or if an impermissible current or voltage value
(too high or too low) has been measured (see device) during the
teaching procedure. The group signal output is not activated.
2
" set to 0 (left stop)
R
" set to > 0 with ramp time set to
R
Order No.: 3ZX1012-0RF00-5AW1
5. Carry out the first storage of the reference power rating (1st teaching
procedure) by pressing the "Test / Teach" key for more than 3 s
under normal operating conditions (voltage and current must not
exceed the specified limit values). The end of the teaching routine is
signaled by the LOAD, THYRISTOR and SUPPLY LEDs lighting up
simultaneously for approx. 1 s (Fig. III). The teaching procedure can
be repeated as frequently as desired.
During the teaching procedure, the set ramp time "t
fully run through. Interruptions during this period are not possible.
Operation
The power controller can be switched on using the following options:
• Fig. IVa: By pressing the "Test / Teach" key for less than 1 s for test
purposes.
• Fig. IVb: Via the debounced control input "IN / 0 –" with the setting
switch "P" in the > 0 position (also refer to Fig. IIa).
• Fig. IVc: Via the analog input "10 V +" with the setting switch "P" in 0
position (also refer to Fig. IIb).
The "INPUT" LED will light up if one of the three ON signals are output.
The "ON" LED will light up when there is current flow.
Fault monitoring
The LEDs display the following faults:
• LOAD:
A partial load fault occurs when at least one of up to 6 partial loads
fails (partial load faults are only detected in the 20 to 100 % control
range).
• THYRISTOR:
Thyristor fault occurs if no current flow is detected without an ON
signal being available.
• SUPPLY:
Supply fault occurs if there is an ON signal and no current flow is
detected, or if the supply voltage is too low or not available (see
device).
The faults displayed by the LEDs are signaled as a group signal via a
NC contact (terminals 11, 12).
Overload and short-circuit protection
The operator is responsible for providing sufficient overload and short-
circuit protection for the respective applications.
3RF29.0-0KA..
u
s
DIN EN 60947-4-3
English
" (max. 10 s) is
R

Advertisement

loading

This manual is also suitable for:

Sirius 3rf2990-0ka16