4.6
Expansion Module MAC00-FP2/FP4
4.6.2
MAC00-FP2 and FP4 Address and Termination setup
Each unit connected to the Profibus must be set up with a unique address.
The illustration below shows how the address and termination can be set on the internal
dip switch. The dip switch is located on the internal circuit board.
JVL Industri Elektronik A/S - User Manual - Integrated Servo Motors MAC050 - 800
MAC00-FP2 and FP4 Dip switch settings
Dip 1-7 - Address setting
(address range 0-127)
Dip 8 - Address set by software
Dip 9-10 - Line termination
Both set to ON =
Term. enabled
Both set to OFF =
Term. disabled
Notes.
SW1 default setting: All switches set to "ON"
except 9+10 which are "OFF" which corresponds to
- Address is set by software / - Termination disabled
"Address set by software" (DIP8) means that
the profibus address will automatically be set
to the same value as the motor address
Cable glands
Profibus and I/O
connectors.
Rear side of the MAC00-FP2 or FP4
Mini dip-switch
expansion module
OFF
ON
1
2
3
4
5
6
7
8
9
0
SW1
Dip switch location on the
MAC00-FP2 Expansion module
Internal circuit boards
Dip Switch placed
on the rear side of the
module
Basic MAC motor
housing
TT0946GB