02/16 MN05013001Z EN
j
ES4P
U
= 300/500 V
e
EASY...-AC-...E

Remote standard expansion

Remote expansion units can be installed and run up to 30 m
away from the basic unit.
Danger!
The two-wire or multiple-wire cable between the devices
must adhere to the insulation voltage requirement which
is stipulated for the installation environment. Otherwise, a
fault (ground fault, short-circuit) may lead to the
destruction of the units or injury to persons.
A cable, such as NYM-0 with a rated operational voltage
U
= 300/500 V AC, is normally sufficient.
e
EASY200-
EASY
E+ E–
Figure 31: Connecting remote standard expansion devices to
easySafety
h
Terminals E+ and E– of the EASY200-EASY are protected
against short-circuits and polarity reversal.
Functionality is only ensured if E+ is connected with E+
and E– with E–.
Expanding inputs/outputs
E+ E–
EASY6..RE/TE
75