450
e Contacts OS..Q1 to Q5: Close on acceptance of the selected
operating mode and enable it.
Use only in the safety circuit diagram.
f Contact OS..ER: Closes in the event of an error.
Use in the safety and in standard circuit diagram.
g Diagnostics output OS..DG: Provides information about the
states of the function block.
Evaluation only in the standard circuit diagram with the diag-
nostics function block DG.
Wiring of the function block
Wire its coils OS..I1 to OS..I5 directly with the device termi-
nals IS1 to IS14. Example of an operating mode switch with
5 switch positions:
IS01---------------------------Ä OS01I1
IS02---------------------------Ä OS01I2
IS03---------------------------Ä OS01I3
IS04---------------------------Ä OS01I4
IS05---------------------------Ä OS01I5
IS06---------------------------Ä OS01SM
IS07---------------------------Ä OS01UL
Figure 229:
Wiring of input coils
The function block contacts OS..Q1 to OS..Q5 can be used
for the further processing in the circuit diagram. Example:
L
OS01Q1---------------------------Ä MS01
OS01Q2---------------------------Ä MS02
OS01Q3---------------------------Ä MS03
OS01Q4---------------------------Ä MS04
OS01Q5---------------------------Ä MS05
Figure 230:
Wiring the contacts of the operating mode switch
to safety markers