Safety function blocks
Status number
Hexadecimal (0–F)
0000
2001
2002
2003
2004
2005
200E
8005
F001
F00B
F00E
398
Outputs
The actual value output QV: Indicates the current actual
value of the discrepancy time.
Diagnostics output DG: Provides information the states of
the function block. It is evaluated in the standard circuit
diagram e. g. with the diagnostics function block.
Parameters
QV:
DG:
Table 15:
Diagnostics-/-Error codes
Plain text
decimal (0-9)
0000
No Enable.
8193
Enable issued; waiting for first (or only) input.
8194
Waiting for second input.
8195
Waiting for rising edge at Reset.
8196
Waiting for falling edge at Reset.
8197
Only one channel has been opened.
8206
Waiting for inputs during startup testing.
32773
Light curtain free (QS = 1).
61441
Error: Discrepancy time expired.
61451
Error: Reset and inputs operated on function block
startup.
61454
Error: Only one channel was opened and closed.
Further information on these outputs is provided in section
"Common features", page 348.
02/16 MN05013001Z EN
Function, parameterisation in the func-
tion block
Actual value discrepancy time: Time
Diagnostics: double word a table 15