easySafety Settings
600
Deleting retentive actual values of markers and func-
tion blocks
The retentive actual values are cleared if the following is
fulfilled (applies only in STOP mode):
• When transferring the circuit diagram from the easySoft-
Safety (PC) or memory card to the easySafety, the reten-
tive actual values are reset to 0, provided that the RETAIN
MARKERS option has not been selected. This also applies
when there is no program on the memory card; in this case
the old circuit diagram is retained in easySafety.
• When changing the respective retentive range.
• When the circuit diagram is deleted via the DELETE PROG
menu.

Retain retentive markers during transfer

Selecting the RETAIN MARKERS option tells the device that
it must handle the retentive markers as recipe markers. This
means that the states of these markers are not changed by
a configuration transfer (using the configuration software or
the external memory card) nor by editing the circuit diagram
on the device.
However, the retentive markers will be cleared in the
following circumstances even if the RETAIN MARKERS
option is activated:
• if the DELETE ALL item in the device's System menu is
selected;
• if the retentive marker ranges are changed with the
device's System menu item STD PARAMETERS...,
SYSTEM..., RETENTION...;
• if the retentive marker range has been modified through a
transfer from the configuration software or the external
memory card.