Safety function blocks
Status number
Hexadecimal (0–F)
0000
2001
2005
2016
2017
2018
800B
F006
F00E
F018
484
Output
Diagnostics output DG: Provides information the states of
the function block. It is evaluated in the standard circuit
diagram e. g. with the diagnostics function block.
Parameters
DG:
Table 21:
Diagnostics-/-Error codes
Plain text
decimal (0-9)
0000
No Enable.
8193
Enable issued; waiting for first (or only) input.
8197
Only one channel has been opened.
8214
Two-hand pushbutton in normal position.
8215
Two-hand pushbutton 1: undefined position.
8216
Two-hand pushbutton 2: undefined position.
32779
Two-hand pushbutton operated (QS = 1).
61446
Error: Second pushbutton pressed too late (> 500 ms).
61454
Error: Only one channel was opened and closed.
61464
Error: At least one input operated on function block
startup.
Further information on this output is provided in section
"Common features", page 348.
02/16 MN05013001Z EN
Function, parameterisation in the func-
tion block