Eaton easySafety Manual page 320

Control relay
Table of Contents

Advertisement

Standard function blocks
T 02 X M:S +
>I1
>I2
QV>
316
f Contact T..Q1: Closes on reaching the upper setpoint.
g Output T ..QV: Outputs the currently elapsed time.
Wiring of the function block
You wire the function block in the standard circuit diagram
with its coils and contact.
Timing relay example:
IS10-----------------------------Ä T 03EN
M 42-----------------------------Ä T 03RE
M 43-----------------------------Ä T 03ST
Figure 153: Wiring the function block coils
The trigger coil of the function block is connected here
directly to the device inputs. A marker activates the reset
coil, another marker activates the stop coil.
T 03Q1---------------------------Ä QS01
Figure 154: Wiring of the function block contact
The function block indication signal is assigned directly to a
device output.
Parameters
When using the function block in the circuit diagram for the
first time, use OK to automatically enter the general display
of function block parameters, as shown in the figure on the
left. Enter the function block settings here. The display
contains the following elements:
Function block: Timing relay, number 02
T 02
Operating mode: On-delayed
X
Time range: Minute: Seconds
M:S
Parameter display: Call enabled
+
Setpoint 1
>I1
Setpoint 2 (for relay functions with 2 times)
>I2
Display: Elapsed time
QV>
02/16 MN05013001Z EN