Dg, Diagnostics - Eaton easySafety Manual

Control relay
Table of Contents

Advertisement

02/16 MN05013001Z EN

DG, diagnostics

The diagnostics function block (DG function block) evaluates
the status messages of a safety function block. A status
message is connected in the standard function block
diagram with a contact of the DG function block. The contact
closes if the message occurs. This can be responded to in the
user program: To do this create a text using the text display
function block. After the contact closes, the text can be
shown on the display or on a connected visualization device.
The DG function block can only be edited with the easySoft-
Safety configuration software. This allows the use of up to
16 diagnostics function blocks.
Function block
DG...
DiaGnostic
a
EN
Figure 98: "Diagnostics" function block
a Coil DG..EN: Enables the operation of the DG function block.
b Contacts DG..Q1 to DG..Q8: Indicates the status of the safety
function block.
c Contact DG..QC: Outputs a group message (OR operation) for
the 8 contacts Q1..Q8.
d Output DG..QV: Supplies the status code from the diagnostics
register of the safety function block.
e Output DG..QN: Supplies the status of all contacts Q1..Q8 of
the DG function block (double word format).
DG, diagnostics
Q1
Q2
Q3
Q4
b
Q5
Q6
Q7
Q8
QC
c
QV>
DW
d
QN>
DW
e
237