Safety function blocks
TS01 S
*** ***
>T1
000
>T2
000
496
Parameters
When using the function block in the circuit diagram for the
X
*
first time, press OK to enter the general display of the func-
tion block parameters automatically, as shown in the figure
on the left for an on-delayed timing relay. Enter the function
block settings here. The display contains the following
elements:
TS01
X
S
>T1
>T2
The parameters consist of the following:
Operating mode
The Operating mode parameter defines the switch function
of the timing relay.
Parameters
X
â
Xâ
#
ü
Ü
02/16 MN05013001Z EN
Function block: Safety timing relay No. 01
Operating mode: On-delayed
Time range: Seconds
Time value T1: 000s.000ms
Time value T2: 000s.000ms
Switch function
On-delayed switching (one time value required)
Off-delayed switching (one time value required)
On and off-delayed (two time values required)
Off delayed switching, setpoint retriggerable
(one time value required)
Single pulse switching (one time value
required)
Flash switching (two time values required)
Zeitwert