02/16 MN05013001Z EN
– Transistor output: 150 ms + 1 ms = 151 ms
– Relay output: 150 ms + 50 ms = 200 ms
If the calculated circuit diagram processing time is longer
than the detetction time of the easySafety device (150 ms),
the following applies in regard to the reaction time:
Reaction time = circuit diagram processing time + output
delay
– Transistor output:
circuit diagram processing time (ms) + 1 ms
– Relay output:
circuit diagram processing time (ms) + 50 ms
Table 30:
Maximum circuit diagram processing time as a func-
tion of the number current rungs
Number of circuit
connections
1 - 39
40 - 79
80 - 119
120 - 159
160 - 199
200 - 239
240 - 253
1) The maximum circuit diagram processing time is achieved
under maximum load, i.e. the following conditions are
applied to the maximum utilization of the system in addition
to the configuration with safety and standard circuit
diagram:
• Device in the NET with seven other stations.
• Maximum data volume on the NET through the use of the
maximum number of PUT and GET standard function
Reaction time of an easySafety
device
Max. circuit diagram processing
1)
time
[ms]
100
135
170
205
245
275
300