RUN and STOP and BUSY

easySafety has the three operating modes RUN, STOP and
BUSY. The device switches operating mode BUSY only
temporarily when:
• a configuration transfer with easySoft-Safety is being
performed;
• you start the configuration.
In the RUN operating mode, the safety circuit diagram, as
well as the possibly wired standard circuit diagram, are
executed continuously until you select STOP, the internal
device safety monitoring mechanism detects an error or the
supply voltage is turned off.
The safety circuit diagram and the parameters are retained
in the event of a power failure. All you will have to do is reset
the real-time clock after the back-up time has elapsed. In
RUN mode:
• the process image of the inputs are read.
• the safety and standard circuit diagram are processed.
• the process image of the outputs is transferred to the
physical outputs.
In STOP mode neither the safety nor the standard circuit
diagram are run. Only in this mode is circuit diagram entry,
modification of the system parameters or configuration of
the easyNet possible. It is also possible to store the safety
and standard circuit diagram on the external memory card or
load them from the external memory card. In this mode, a
circuit diagram can also be transferred from and to easySoft-
Safety.
Æ
The switch from RUN to STOP and vice versa is carried out in
the main menu.