Safety function blocks
352
Operating mode
After easySafety has determined the conditions for safe
operation, there are different kinds of restarts possible. They
are described in greater detail as operating modes in section
"Operating mode parameter, RE reset coil" on page 346.
Parameters
Function, parameterisation in the func-
tion block
Manual start
MST
Controlled start
CST
Automatic start, no manual restart
AST
The factory setting of this parameter is MST, Manual Start.
Monitoring time
After the EM..OC picks up, the function block monitors
whether the feedback signal via coil EM..FL is generated
within the specified monitoring time.
Parameters
Function, parameterisation in the func-
tion block
0.1 - 3.0 s; adjustable in increments of g? .1 s
>FT
This parameter is factory set to 3.0 s.
Outputs
Actual value output QV: Indicates the current actual value of
the monitoring time.
Diagnostics output DG: Provides information the states of
the function block. It is evaluated in the standard circuit
diagram e. g. with the diagnostics function block.
Parameters
Function, parameterisation in the func-
tion block
QV:
Monitoring time actual value: Time
DG:
Diagnostics: double word a table 11