easySafety internal
610
Delay time with DEBOUNCE activated
When DEBOUNCE is activated, the delay time for DC signals
is 24 ms.
1
S1
0
1
IS1
0
A
B
Figure 293:
Delay times for evaluating an input signal and an
activated DEBOUNCE
An input signal S1 must therefore be > 24 V on the input
terminal for at least 15 ms before the switch contact will
change from 0 to 1 (A). If applicable, this time must also
include the cycle time (B) since a easySafety device does not
detect the signal until the start of a cycle.
When the DC signal drops from 1 to 0 with DEBOUNCE
active, the same delay time (C) of 24 ms applies.
02/16 MN05013001Z EN
C
B
B
B
B