Eaton easySafety Manual page 614

Control relay
Table of Contents

Advertisement

easySafety internal
610
Delay time with DEBOUNCE activated
When DEBOUNCE is activated, the delay time for DC signals
is 24 ms.
1
S1
0
1
IS1
0
A
B
Figure 293:
Delay times for evaluating an input signal and an
activated DEBOUNCE
An input signal S1 must therefore be > 24 V on the input
terminal for at least 15 ms before the switch contact will
change from 0 to 1 (A). If applicable, this time must also
include the cycle time (B) since a easySafety device does not
detect the signal until the start of a cycle.
When the DC signal drops from 1 to 0 with DEBOUNCE
active, the same delay time (C) of 24 ms applies.
02/16 MN05013001Z EN
C
B
B
B
B