How the easySafety device evaluates the safety and
standard circuit diagram as well as the function
blocks
Rung
Segment
1
2
1
IS01----------------------------Ä ES01I1
IS03----------------------------Ä ES01RE
2
ES01QS--------------------------Ä QS01
3
MS02----IS04----MS01------------Ä TS01SA
4
.. ...
n
IS14----------------------------Ä QS04
1
2
1
IS01----IS04-----HW01Q1--T06Q1--Ä T01EN
IS02----IS03--------------------Ä QS02
2
T01---u-------------------------Ä QS01
3
P01---k
4
..
...
IS14-----------------------------Ä QS04
n
Segment 1 - 4
The easySafety device evaluates the contact fields within the
first four segments. The evaluation starts in the first segment
in circuit diagram line 1 of the safety circuit diagram and
continues from top to bottom until circuit diagram line n is
reached. The easySafety device then moves to the next
contact segment and continues to evaluate from top to
bottom until it has reached the last contact in the fourth
segment.