Eaton easySafety Manual page 156

Control relay
Table of Contents

Advertisement

Wiring with easySafety
Circuit diagram:
IS01------Ä :01
IS02------Ä :02
: 01
--------u-ÄQS01
h-RQS02
----------Ä :08
: 02------ÄQS02
QS02-IS03-T T02
T 02------ÄQS01
: 08
I 1 2 -------Ä D01
152
Example
A selector switch is used to select two different sequences.
• Sequence 1: Switch on motor 1 immediately.
• Sequence 2: Activate barrier 2, wait time, then switch on
motor 1.
Contacts and relays used:
Sequence 1
IS1
Sequence 2
IS2
Barrier 2 moved out
IS3
Motor-protective circuit-breaker switched on
IS12
Motor 1
QS1
Barrier 2
QS2
wait time 30.00 s, on-time
T01
Text "Motor-protective circuit-breaker tripped"
D 01
Power flow display: I 01 selected:
IS01======Ä :01
IS02--------:01
: 01
=========uÄQS01
hRQS02
==========Ä :08
: 02======== 08
QS02--IS03--:08
T 02--------:08
: 08
IS 1 2 ------Ä D01
02/16 MN05013001Z EN
Range from jump label 1 processed.
Jump to label 8.
Range to jump label 8 skipped.
Jump label 8, circuit diagram