Installation
54
h
Power the transistor outputs with voltage!
If the transistor outputs are not supplied, the easySafety
will generate a category B fault, a page 622. This
causes all outputs to be switched off.
h
Take into account the time behaviour of the transistor
outputs when choosing the actuator that the easySafety
device will be actuating. (a „Time behaviour of the
inputs and outputs", page 608).
EASY6..-DC-TE (standard expansion device)
S1
S2
0 V H
+ 24 V H
24 V H
(20.4 – 28.8 V H)
Figure 19: EASY6..-DC-TE transistor outputs
Parallel connection:
Up to four outputs can be connected in parallel in order to
increase the power. This enables a maximum output current
of 2 A.
02/16 MN05013001Z EN
S3
S4
S5
S6
S7
f 2.5 A
R
L
0.5 A
0.5 A
5 W/24 V
24 V
0 V
Q
Q
S8
F 10 A