02/16 MN05013001Z EN
In normal operation, the NET stations organise their data
exchange independently. The NET stations also determine
the minimum delay time required so that all messages can be
sent.
Even if a maximum baud rate is set, it may be necessary to
increase the bus delay time for the following reasons:
• In addition to the user data, additional data is transferred
to the PC, i.e. to easySoft-Pro in online status or to an
MFD-Titan in terminal mode.
• The transfer rate is low.
By increasing the bus delay time you increase the time
window for online services such as the power flow display,
status display of actual values of function block operands
and the forcing of markers.
An increase of the bus delay time is only really necessary in
the following conditions:
• You use an MFD-Titan in terminal mode via the NET and
see the message "Connection establishment in
progress..." In this case the bus delay time must be
increased permanently.
• You wish to use the online services of the easySoft-Safety
configuration software via the NET. In Communication
View, however, you will receive the error message "Device
not responding". This fault message appears if you wish
to establish an online connection or are already online. In
this case, a temporary increase of the bus delay time is
useful. It should be reduced after commissioning.
Remember also that the easySoft-Safety configuration
software displays status changes more quickly on the device
if you select the maximum PC baud rate.
Description of the NET-
PARAMETERs
561