Eaton easySafety Manual page 289

Control relay
Table of Contents

Advertisement

02/16 MN05013001Z EN
Output
Output QV> supplies the converted value.
Parameters
Function, parameterisation in the function
block
Output value:
QV>
Decimal: -161061273 - +161061273
BCD: -9999999 - +9999999
The function block register output NC..QV can have the
following operands:
• Markers MD, MW, MB.
Coil
The coil NC..EN is used to activate the function block in the
standard circuit diagram. If coil NC..EN is not active, the
entire function block is deactivated and reset. The output
value is set to zero.
Coil
Function
Selective activation of the function block
NC..EN
Memory requirement
The numerical converter function block requires 32 bytes of
memory plus 4 bytes per constant at the function block
input.
Operation of the function block
BCD mode
The BCD value present at input I1 is converted to a binary
value and supplied on the output QV>. The binary value is
displayed as a decimal value.
Example 1:
Input value >I1: +9
dec
Binary value: 1001
Decimal value QV>: + 9
NC, numerical converter
285