Eaton easySafety Manual page 630

Control relay
Table of Contents

Advertisement

easySafety internal
MODULE ID
06
11
24/25
63/101
64/102
65/103
66/104
67/68
1)
85
1)
86
1)
87
1)
88
1) Do not apply any test signals to inputs that have not been assigned a test signal. In this case,
easySafety may generate an error message during the power up and prevent the automatic switch
to RUN mode. (a chapter "easySafetyoperating modes", page 79)
626
Possible fault and troubleshooting information
There are deviations between the configuration in the device and on the
inserted card:
• The device stored on the card is not the actual device.
• The safety circuit diagram stored on the card is not the same as that in the actual
device.
This error cannot occur if the "Allow card overwriting" option has been acti-
vated.
There is a short circuit to 24 V DC or GND on a transistor. Check the wiring
of the outputs.
The 24 V DC power supply of the transistor output is not provided. Feed the
transistor outputs with 24 V DC or check the terminal connection for
possible incorrect polarity.
Short-circuit to 24 V DC. Check the wiring at QS1.
Short-circuit to 24 V DC. Check the wiring at QS2.
Short-circuit to 24 V DC. Check the wiring at QS3.
Short-circuit to 24 V DC. Check the wiring at QS4.
The configuration on the device is damaged. Use easySoft-Safety or the
memory card to transfer the configuration to the device.
Error on test signal cable T1
Error on test signal cable T2
Error on test signal cable T3
Error on test signal cable T4
02/16 MN05013001Z EN
Possible errors include, for example:
cross-circuits between test signal cables
or a short circuit to 24 VDC, or an error in
the assignment to the IS device inputs.
Please check the wiring and routing for
test signals T1-T4. Please also check that
the T1-T4 test signals are correctly
assigned to the device's IS safety inputs.