Standard Connection Diagram - Sink, An Example Of A Standard Connection For 480 V Class, 160 Kw (Frame Size A7) - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

[Standard connection diagram - Sink]
This diagram shows an example of a standard connection for 480 V class, 160 kW (frame size A7).
Power supply
480 V class:
160 kW
Three-phase 380 - 440 V-50 Hz
Three-phase 380 - 480 V-60 Hz
MCCB
2
b-contact of
overload relay
9
*1
Be sure to mount the DC reactor. A circuit between the terminals [PA/+] and [PO] is not short circuited (at the time of shipping).
*2
To input DC power, connect the inverter between the terminals [PA/+] and [PC/-].
*3
When the inverter is used with a DC power, a circuit to suppress an inrush current may be required. Please contact your Toshiba distributor for
information.
*4
When the inverter is used with a DC power supply, three-phase power input for cooling fan driving is required separately..
*5
External braking resistor (option)
*6
For the switch function, refer to [2. 3. 5].
*7
To supply control power from an external power supply for backing up the control power supplied from the inverter, an optional control power supply
unit (CPS002Z) is required. In this case, it is used in conjunction with the inverter internal power supply.
Set <F647: Control power option failure detection> to back up the control power supply.
For details, refer to [6. 30. 20].
*8
The reset signal is activated by ON→OFF trigger input.
*9
Connect to power to comply with OVC2 (Over Voltage Category 2). Isolation transformer is necessary when connecting to power supply (OVC3).
2. Installation and wiring
*1
PO
MC
R/L1
S/L2
T/L3
*4
RO
480/240 V
SO
transformer
TO
RUN
MC
+SU
CC
Optional control
power supply unit
*7
FLA
*9
FLB
Surge
absorber
ON
FLC
RUN
R1A/R2A
OFF
RUN
*9
R1C/R2C
FM AM CC
Frequency
Ammeter
meter
Ammeter or voltmeter
*2
+DC -DC
*3
PA/+
PC/-
PB
U/T1
Power
V/T2
EMC
filter
circuit
W/T3
Fan
DC/DC
F
R
RES
S1
S2
S3
S4
Control
S5
circuit
CC
P24
SINK
FP
PLC
SOURCE
SW1
PLC
*6
STOA
STOB
RX
II
RR PP
External potentiometer
(Or, input voltage signal of 0 - 10 V between the terminals [RR] and [CC])
2-30
E6582062
*5
Motor
M
Digital input
Fwd run
Rev run
*8
Reset 1
Preset speed switching 1
Default
Preset speed switching 2
setting
Preset speed switching 3
Preset speed switching 4
Preset speed switching 5
Common
Pulse counter
Voltage signal: -10 to +10 V
Current signal :4(0) to 20 mA