Selection Of A Wiring Device; Selection Table Of A Wiring Device - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

10. 2 Selection of a wiring device

According to the table [10. 2. 1], select an appropriate wiring device depending on the voltage class and
capacity of the inverter.
10. 2. 1
Select a wiring device depending on the inverter type and input current in the table next.
■ Wiring devices for HD rating
Voltage
class
3-phase
240 V
9
10
10. Selection and installation of peripheral devices

Selection table of a wiring device

Applicable
Inverter type-form
motor (kW)
0.4
VFAS3-
2004P
0.75
2007P
1.5
2015P
2.2
2022P
4.0
2037P
5.5
2055P
7.5
2075P
11
2110P
15
2150P
18.5
2185P
22
2220P
30
2300P
37
2370P
45
2450P
55
2550P
Molded-case circuit
Input current (A)
breaker (MCCB)
Earth leakage circuit
breaker (ELCB)
1.7
3.3
6.0
9.0
15.1
20.1
27.3
40.0
53.2
64.8
100
78.3
100
104.7
150
128.4
175
157.6
200
189.0
250
10-4
E6582062
Rated current (A)
Magnetic contactor
(MC)
3
20
5
20
10
20
15
20
20
20
30
32
40
32
50
50
75
60
80
80
150
200
260
260

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents