6) Motor parameter setting method (Advanced)

• How to adjust the moment of inertia of the load
<F459: Load inertia ratio>
This parameter adjusts the excess response speed.
Increasing this value will reduce the overshoot at the acceleration/deceleration completion
point.
Default setting values are set so that the moment of inertia of the load (including the motor
shaft) value is set to be appropriate at 100% of the motor shaft. If the moment of inertia of the
load is not 100%, set a value appropriate for the actual moment of inertia of the load.
<F461: Speed control stabilization coefficient 1>
<F462: Speed reference filter coefficient 1>
<F463: Speed control response 2>
<F464: Speed control stabilization coefficient 2>
<F465: Speed reference filter coefficient 2>
<F466: Speed control response switching frequency>
This parameter adjusts the excess response speed.
Increasing this value will reduce the overshoot at the acceleration/deceleration completion
point. Set a value appropriate for the actual moment of inertia of the load.
• If the torque needs to be increased in low speed range (10Hz or less as a guide)
Perform the basic settings for the motor parameters. Then, if the torque needs to be
increased even further, increase <F413: Exciting current coefficient> to a maximum of 130%.
<F413> is a parameter that increases the magnetic flux of the motor at low speeds, so
specifying a higher value for <F413> increases the no-load current. If the no-load current
exceeds the rated current, do not adjust this parameter.
• If the motor stalls when operated at frequencies over the base frequency
Adjust <F414: Stall prevention coefficient>.
If a heavy load is applied momentarily (transiently), the motor may stall before the load
current reaches the stall prevention level (<F601>, etc.). In such a case, a motor stall may be
avoided by reducing the value of <F414> gradually.
• To use vector control, the motor capacity must be the same as the inverter rated capacity, or
Memo
you can use a general purpose squirrel-cage motor with capacity no less than one rank below.
Note that the minimum applicable motor capacity is 0.1 kW.

■ Online auto-tuning setting

<F403: Online auto-tuning> is a function that automatically adjusts motor parameters by predicting
the increase in motor temperature.
• Online auto-tuning must be performed along with <F400: Offline auto-tuning>.
• Perform auto-tuning when the motor has cooled down (same temperature as the ambient
temperature).
7) Parameter setting
6-87
E6582062