■ Guideline for the setting
When you want to use the terminal [S4], set <F146: Terminal S4 input select> to "1: Pulse train
input". When you want to use the terminal [S5], set <F147: Terminal S5 input select> to "1: Pulse
train input".
Set the number of pulses per 1 Hz of output frequency at <F378; Pulse train input pulses number>.
The minimum number of pulses that can be input to the terminals [S4] and [S5] is 10 pps, and the
maximum number of pulses 30 kpps. The duty is 50 ±10%.
The maximum frequency that can be output is 200 Hz.
■ Setting example
<F378> setting value
4
4
6
Reference
9
6. [Advanced] How to use parameters
25 (pps)
50 (pps)
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3].
Details on operation by external signals -> Refer to [Chapter 7].
Input signal
25 (pps)
100 (pps)
2k (pps)
50 (pps)
100 (pps)
2k (pps)
6-28
E6582062
Output frequency
1.0 (Hz)
4.0 (Hz)
80.0 (Hz)
1.0 (Hz)
2.0 (Hz)
40.0 (Hz)