Output Terminal Function - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

11. 9

Output terminal function

The function No. in the following table can be assigned to parameters <F130>, <F132>-<F134>,
<F137>, <F138>, and <F159>-<F163>.
Function Number
Symbol
Positive
Negative
logic
logic
0
1
LL
2
3
UL
4
5
LOW
6
7
RCH
8
9
RCHF
10
11
FL1
12
13
FL2
14
15
POC
16
17
POLI
18
19
POLM
20
21
POH
22
23
POP
24
25
MOFF
26
27
UC
28
29
OT
30
31
POLR
Function
Lower limit frequency (LL) ON: Output frequency over <LL: Lower limit frequency>
Upper limit frequency
ON: Output frequency is <UL: Upper limit frequency> or more
(UL)
ON: Output frequency is <F100: Low-speed signal output
Low-speed signal
frequency> or more
Output frequency is within command frequency ± <F102:
Acc/Dec completed
Reach signal detection band>
Specified frequency
ON: Output frequency is within <F101: Reach signal
attainment
specified frequency> ± <F102: Reach signal detection band>
Failure signal 1
ON: Tripped
Failure signal 2
ON: At trip, except "EF", "OCL", "EPHO", and "OL2"
Overcurrent (OC) pre-
ON: Output current is <F601: Stall prevention level 1> or
alarm
more
Inverter overload (OL1)
ON: Calculated value of overload protection level is a specific
pre-alarm
level or more
Motor overload (OL2)
ON: Calculated value of overload protection level is <F657:
pre-alarm
Overload alarm level> or more
ON: Approx. 95°C or more of IGBT element
Overheat (OH) pre-alarm
OFF: Under approx. 95°C of IGBT element (90°C or less
after detection is turned on)
Overvoltage (OP) pre-
ON: Overvoltage limit in operation
alarm
Power circuit undervolt-
ON: Main circuit undervoltage (MOFF) detected
age (MOFF) alarm
ON: When the output current falls below the value set by
<F611: Undercurrent detection level> and remains below
<F611: Undercurrent detection level>+<F609: Undercurrent
Undercurrent (UC) alarm
detection hysteresis> for the period of time specified by
<F612: Undercurrent detection time>
OFF: Output current is over <F611> (<F611>+<F609> or
more after detection turns on)
ON: When the torque becomes <F616: Overtorque detection
level during power running> or more, and remains over
<F616: Overtorque detection level during power running> -
Overtorque (OT) alarm
<F619: Overtorque detection hysteresis> for the time speci-
fied by <F618: Overtorque detection time>
OFF: Torque is under <F616> (<F616>-<F619> or less after
detection turns on)
Braking resistor overload
ON: 50% or more of calculated value of <F309: Braking
(OLr) pre-alarm
resistor capacity> set overload protection level
11-61
E6582062
Action
11. Table of parameters
Reference
1
[7. 2. 2]
[7. 2. 2]
3
[6. 1. 1]
[7. 2. 2]
[6. 1. 2]
[7. 2. 2]
[6. 1. 3]
[7. 2. 2]
[6. 30. 5]
[6. 30. 6]
[6. 30. 7]
[6. 30. 8]
[6. 30. 10]
[6. 30. 14]
[7. 2. 2]
9
10
[7. 2. 2]
11
[6. 30. 7]
[7. 2. 2]
[6. 30. 8]
[7. 2. 2]
[6. 15. 4]
[7. 2. 2]