<F229: AI5 point 1 frequency>
<F230: AI5 point 2 input value>
<F231: AI5 point 2 frequency>
<F810: Communication frequency point select>
<F811: Communication point 1 input value>
<F812: Communication point 1 frequency>
<F813: Communication point 2 input value>
<F814: Communication point 2 frequency>
■ Function
These parameters set the output frequencies for the frequency commands of the analog signals.
You can use the following terminals. The terminals [AI4] and [AI5] are optional.
Voltage input (0 to 10 V)
Voltage input (-10 to +10 V) : terminals [RR], [RX], [AI4], and [AI5]
Curret input (4 to 20 mA)
■ Parameter setting
Title
Parameter name
F107
Terminal RX input
voltage select
F108
Terminal RR input select
F148
Terminal AI4 input select
F149
Terminal AI5 input select
F201
RR point 1 input value
F202
RR point 1 frequency
F203
RR point 2 input value
F204
RR point 2 frequency
F205
RR point 1 rate
F206
RR point 2 rate
F209
Analog input filter
: terminals [RR], [RX], [AI4], and [AI5]
: terminals [II], [AI4], and [AI5]
Adjustment range
0: 0 to +10 V
1: -10 to +10 V
1: Voltage input (0-10 V)
2: -
3: -
4: PTC input
5: PT100 (2-wire) input
6: -
7: PT1000 (2-wire) input
8: -
9: KTY84 input
1: Voltage input (0-10 V)
2: Voltage input (-10 to +10 V)
3: Current input (0-20 mA)
4: PTC input
5: PT100 (2-wire) input
6: PT100 (3-wire) input
7: PT1000 (2-wire) input
8: PT1000 (3-wire) input
9: KTY84 input
0-100
0.0-590.0
0-100
0.0-590.0
0-250
0-250
1: Disabled
2-1000
6-21
E6582062
Unit
Default setting
-
0
-
1
-
1
1
%
0
Hz
0.0
%
100
Hz
*1
50.0/60.0
%
0
%
100
1
ms