Displaying Frequency By Converting To Other Unit; Parameters Converted With <702: Free Unit Multiplication Factor> - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

(3)

Displaying frequency by converting to other unit

<F702: Free unit multiplication factor>
<F703: Target of free unit>
<F705: Free unit inclination polarity>
<F706: Free unit bias>
■ Function
The monitor display and the frequency display of parameters can be converted into the motor speed
or load speed.
The unit of the set value or that of feedback can be changed at PID control for easy setting.
■ Parameter setting
Title
Parameter name
F702
Free unit multiplication
factor
F703
Target of free unit
F705
Free unit inclination
polarity
F706
Free unit bias
■ Reference of setting
The value obtained by multiplying the displayed frequency by the setting value of <F702: Free unit
multiplication factor> is displayed.
"Value displayed" = "Monitor-displayed" or "parameter-set frequency" x <F702>
■ Parameters converted with <702: Free unit multiplication factor>
When <F703: Target of free unit> is "0"
It applies to all the frequency.
• Frequency monitor display: Frequency command value, Output frequency, PID feedback value,
Stator frequency, During stop: Frequency command value (During run: Output frequency)
• Frequency-related parameters: <FC>, <FH>, <UL>, <LL>, <FPId>, <Sr0> - <Sr7>, <F100>,
<F101>, <F102>, <F190>, <F192>, <F194>, <F196>, <F198>, <F202>, <F204>, <F208>,
<F211>, <F213>, <F217>, <F219>, <F223>, <F225>, <F229>, <F231>, <F235>, <F237>,
<F240>, <F241>, <F242>, <F243>, <F244>, <F250>, <F260>, <F265>, <F267>, <F268>,
<F270> - <F275>, <F287> - <F294>, <F321>, <F322>, <F330>, <F331>, <F346>, <F350>,
<F352>, <F355>, <F364>, <F365>, <F367>, <F368>, <F370>, <F371>, <F374>, <F383>,
<F391> - <F393>, <F426>, <F428>, <F431>, <F432>, <F466>, <F505>, <F513>, <F517>,
<F606>, <F623>, <F624>, <F643>, <F649>, <F812>, <F814>, <F964> - <F979>
F702
Min: 0.00
X1000
Adjustment range
0.00: Disabled
0.01 - 200.0
0: All frequencies
1: PID frequencies
0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
0.00 - FH
5-75
5. [Fundamental operation] How to use parameters
E6582062
STOP
0.0Hz
15:37
:Free unit multiplying factor
0.00
Max: 200.00
X100
X10
X1
Default
Unit
setting
times
0.00
-
0
-
1
Hz
0.00
3
4
5
9