Setting Number Of Starting Alarm And Alarm Occurrence Of The Specified Trip; Signal Output Of The Number Of Starting Alarm Of The Inverter; Signal Output Of The Number Of External Equipment Starting Alarm - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 30. 21 Setting number of starting alarm and alarm
occurrence of the specified trip
<F648: Number of starting alarm>
<658: Number of external equipment starting alarm>
<664: Specified trip 1>
<665: Specified trip 2>
<F666: Specified trip 3>
■ Function
This parameter counts the number of starting of the inverter, and when it reaches the value set by
<F648: Number of starting alarm>, it outputs the alarm and confirm it in [Monitor mode].
For number of external equipment starting alarm, you can outputs the alarm and confirm it in
[Monitor mode]. For number of starting for external equipment, the number of input to the input
terminal is counted.
Also, occurrence of the specified trip can be confirmed in [Monitor mode].
■ Parameter setting
Title
Parameter name
F648
Number of starting alarm
F658
Number of external
equipment starting alarm
F664
Specified trip 1
F665
Specified trip2
F666
Specified trip3

■ Signal output of the number of starting alarm of the inverter

This parameter counts the number of starting of the inverter, and when it reaches the value set by
<F648: Number of starting alarm>, it outputs the alarm and confirm it in [Monitor mode].
Output alarm
 Assign "162: Number of starting alarm" to the unused output terminal. For details, refer to [7. 2. 2].
[Monitor mode]
 Set "100: Number of starting" to <F711: Monitor mode 1 display> through <F718: Monitor mode 8
display>. For details, refer to [8. 1. 1].

■ Signal output of the number of external equipment starting alarm

This parameter counts the number of starting of the external equipment, and when it reaches the
values set by <F658: Number of external equipment starting alarm>, it outputs the alarm and can be
confirmed in [Monitor mode].
For Number of starting for external equipment, a signal to the input terminal with the function of "114:
External equipment counter" is assigned is counted.
Output alarm
F648 : Number of starting alarm
Min: 0.0
X1000
Adjustment range
0 - 999.0
0 - 999.0
0 - 1 00
0 - 1 00
0 - 1 00
6-151
E6582062
STOP
0.0Hz
14:06
0.0
Max: 999.0
X100
X10
X1
Unit
Default setting
x10,000 times
999.0
x10,000 times
999.0
Times
0
Times
0
Times
0
6. [Advanced] How to use parameters
3
4
6
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents