Switching Of Slide Switch Of Control Terminal Block; Sink Logic And Source Logic - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Wire size
Conductor
Solid wire
Relay
Stranded wire
Solid wire
Except Relay
(2nd)
Stranded wire 0.14-1.5mm
Solid wire
Except Relay
(1st)
Stranded wire 0.14-1.5mm

■ Switching of slide switch of control terminal block

With the slide switch [SW1] of the control terminal block, the setting of sink logic, source logic and
external power supply sink logic of the digital input terminals [F], [R], [RES], and [S1] - [S5] is
switched.
For details of sink/source logic, refer to the following "■Sink logic and source logic."
• The slide switch [SW1] is set to the PLC side in the default setting. This is the setting when the
inverter external power supply is used
• To use as sink logic, set the slide switch [SW1] to the SINK side.
• To use as source logic, set the slide switch [SW1] to the SOURCE side.
• Switch the logic before turning on the power supply.
• After confirming that the sink/source setting is correct, turn on the power supply.
Important

■ Sink logic and source logic

In Japan and the U.S., current flowing out turns digital input terminals on. This is called sink logic.
The method generally used in Europe is source logic in which current flowing into digital input termi-
nals turns them on.
Each digital input terminal is supplied with electricity from either the inverter's internal power supply
or an external power supply, and its connections vary depending on the power supply used.
• Sink logic is sometimes referred to as negative logic, and source logic is referred to as positive
Memo
logic.
Using one wire
2
AWG
(mm
)
0.14-2.5
26-14
2x0.14 to 2x0.75
0.14-2.5
26-14
2x0.14 to 2x0.75
0.14-2.5
26-14
2x0.14 to 2x1.0
2
26-16
2x0.14 to 2x0.75
2
26-16
2x0.14 to 2x0.75
0.14-1.5mm
2
26-16
2x0.14 to 2x0.75
2-49
Using two wires
2
AWG
(mm
)
(mm
26-18
26-18
2x0.5 to 2x1.5
26-18
26-18
2x0.5 to 2x1.0
26-18
26-18
2x0.5 to 2x1.0
E6582062
Using two wires
with twin ferule
2
AWG
)
-
-
20-16
-
-
20-18
-
-
20-18
10
2. Installation and wiring
2
3
9

Hide quick links:

Advertisement

Table of Contents
loading