2.2.1

Standard connection diagram 1

This diagram shows a standard wiring of the main circuit.
Main circuit power supply
1ph-120V class: single-phase 100-120V
-50/60Hz
1ph-240V class: single-phase 200-240V
-50/60Hz
3ph-240V class: three-phase 200-240V
-50/60Hz
MCCB(2P)
Power supply
R/L1
Single phase
S/L2
*1: The T/L3 terminal is not provided
for single-phase models.
Use the R/L1 and S/L2 terminal as
input terminals.
*2: The inverter is supplied with the PO
and the PA/+ terminals shorted by
means of a shorting bar.
Before installing the DC reactor (DCL),
remove the bar.
*3: When using the OUT output terminal in
sink logic mode, short the NO and CC
terminals.
*4: 1ph-240V models have noise filter inside.
*5: 1ph-120V models cannot be used with
DC reactors.
*6: When external potentiometer is
connected by using P5 terminal,
set the parameter  = .
Standard connection diagram - SINK (Negative) (common:CC)
DC reactor (DCL)
*2 , *5 (option)
MCCB
R/L1
S/L2
Noise
T/L3
filter
*1
FLC
FLB
Protective function
activation output
FLA
FM
+
Meter
Frequency
m eter
(am m eter)
-
7.5V-1mA
(or 0-10V/4-20mA)
B-3
P0
PA/+
PC/-
Power
circuit
*4
Control
circuit
VF-nC3
Operation panel
OUT
Connector for
RS485
common serial
communication
communications
connector
CC
VI
P5
External potentiometer (1~10kΩ)
E6581595
Motor
U/T1
V/T2
I M
W/T3
F
Forward
R
Reverse
S1
Preset-speed 1
S2
Preset-speed 2
Common
CC
P24
Low-speed
signal output
Ry
NO
*3
CC
+
Voltage signal: 0-5V/0-10V
-